张功望,王渝红,张 超,杨东斌,左 坤,欧 林.德宝直流系统与宝二扩建机组SSO仿真分析[J].电测与仪表,2014,51(16):1-5.
ZHANG Gong-wang,WANG Yu-hong,ZHANG Chao,YANG Dong-bin,ZUO Kun,OU Lin.Simulation analysis on Subsynchronous Oscillation between Baoji No.2 Power Plant Extension Unit and De-Bao HVDC System[J].Electrical Measurement & Instrumentation,2014,51(16):1-5.
德宝直流系统与宝二扩建机组SSO仿真分析
Simulation analysis on Subsynchronous Oscillation between Baoji No.2 Power Plant Extension Unit and De-Bao HVDC System
DOI:
中文关键词:  高压直流输电系统  次同步振荡  机组作用系数法  复转矩系数法  孤岛运行
英文关键词:HVDCtransmission  system, subsynchronous  oscillation, unit  interaction factor (UIF) , Complex  torque coefficient  method, isolated  island operation
基金项目:国家自然科学基金项目(重点项目)(51037003);国家电网公司科技项目(JXGS-20121123)
                 
作者中文名作者英文名单位
张功望ZHANG Gong-wang陕西省电力公司检修公司
王渝红WANG Yu-hong四川大学电气信息学院
张 超ZHANG Chao四川大学电气信息学院
杨东斌YANG Dong-bin陕西省电力公司检修公司
左 坤ZUO Kun陕西省电力公司检修公司
欧 林OU Lin四川大学电气信息学院
摘要点击次数: 1423
中文摘要:
      针对德宝±500 kV高压直流输电系统可能引起附近汽轮发电机组次同步振荡(SSO)的问题,采用机组作用系数法(UIF)和复转矩系数法对宝鸡换流站附近汽轮发电机组进行风险评估。运用综合程序(PSASP)计算了典型运行方式下宝鸡换流站换流母线的短路容量,由机组作用系数法(UIF)分析得出宝二扩机组不会产生次同步振荡。鉴于冬小孤岛运行方式下的UIF相对较大,进而利用复转矩系数法在PSCAD/EMTDC中搭建电磁暂态仿真模型进行时域仿真校验,复转矩系数法时域仿真得到的结论与机组作用系数法一致。文中分析对于直流输电系统送端引起附近火电机组间的次同步振荡问题具有参考价值。
英文摘要:
      To evaluate the Possibility of subsynchronous oscillation between the turbine-generator unit and ±500 kV direct current transmission system from Baoji to Deyang, the unit interaction factor (UIF) analysis and complex torque coefficient method are adopted for risk assessment. The short-circuit capacities under typical operation modes at Baoji converter station ac bus are calculated using PSASP program,and the UIF shows that Baoji No.2 power plant extension unit doesn’t produce subsynchronous oscillation. Since the UIF of island operation mode in winter-base case is relatively larger to others, complex torque coefficient method is used to do time-domain simulation for Verification using electromagnetic transient simulation model in PSCAD/EMTDC. The results obtained from time-domain simulation conform to the unit interaction factor method. The analysis can be used as reference to subsynchronous oscillation problem resulted from direct current transmission system and power plant units nearby.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司