宋永佳,温才权,李宁,禤海贞,吴志祥,周凯,朱光亚,万航.电缆出线变电站连续两次雷击仿真及防护措施[J].电测与仪表,2018,55(12):115-119.
SONG Yongjia,WEN Caiquan,LI Ning,XUAN Haizhen,WU Zhixiang,ZHOU Kai,ZHU Guangya,WAN HANG.Simulation and Srotection Measures for Two Consecutive Lightning Strikes of Cable Outlet Substation[J].Electrical Measurement & Instrumentation,2018,55(12):115-119.
电缆出线变电站连续两次雷击仿真及防护措施
Simulation and Srotection Measures for Two Consecutive Lightning Strikes of Cable Outlet Substation
DOI:
中文关键词:  雷电绕击  PSCAD  电缆长度  第二次雷击  热备用状态
英文关键词:lighting  failure, PSCAD, length  of cable, the  second lightning  strike, hot  standby mode
基金项目:纳米复合填充物对水树的修复及其在多因子老化下的作用机理研究(基金编号:51477106)
                       
作者中文名作者英文名单位
宋永佳SONG Yongjia南方电网超高压输电公司梧州局
温才权WEN Caiquan南方电网超高压输电公司梧州局
李宁LI Ning南方电网超高压输电公司梧州局
禤海贞XUAN Haizhen南方电网超高压输电公司梧州局
吴志祥WU Zhixiang四川大学
周凯ZHOU Kai四川大学
朱光亚ZHU Guangya四川大学
万航WAN HANG四川大学
摘要点击次数: 2105
中文摘要:
      针对某电缆出线变电站近区连续遭受两次雷电绕击的事故,基于PSCAD/EMTDC搭建仿真模型并进行了过电压的仿真计算。雷击点位于变电站进线第二基杆塔处,仿真分析了发生第一次雷电绕击时,绝缘子片数和出线电缆的长度对绕击过电压的影响,以及发生第二次绕击时不同的避雷器配置方案对热备用状态下断路器过电压的影响。仿真结果表明,绝缘子片数的增加会增大绕击过电压幅值,不同电缆长度对限制过电压的效果具有明显的差异;发生第二次雷击时,通过在站内断路器断口侧及变电站第一基杆塔绝缘子旁安装避雷器,能够有效减小断路器过电压幅值。
英文摘要:
      Based on PSCAD / EMTDC simulation software, the simulation of the overvoltage is carried out for the accident of two lighting failure in a substation near the cable outlet. Lightning point is located in the substation line into the second base tower. When the first lightning strike occurs, the number of insulators and the length of the outgoing cable on the overvoltage are simulated and analyzed. And the influence of different arrester configuration schemes on the over-voltage of the circuit breaker under the standby condition is analyzed. Simulation results show, as the number of insulators increases, the magnitude of the overvoltage will increase, the effect of different cable lengths on limiting overvoltages is quite different; when a second lightning strike occurs, the surge voltage can be effectively reduced by installing the surge arrester at the side of the breaker and the first base tower insulator in the substation.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司