周军,刘毕杰,李曙光.基于改进变频二次注入法的直流系统绝缘检测技术[J].电测与仪表,2019,56(16):129-133.
Zhou Jun,Liu Bijie,Li Shuguang.Insulation detection technology of DC system based on improved frequency conversion two injection method[J].Electrical Measurement & Instrumentation,2019,56(16):129-133.
基于改进变频二次注入法的直流系统绝缘检测技术
Insulation detection technology of DC system based on improved frequency conversion two injection method
DOI:10.19753/j.issn1001-1390.2019.016.021
中文关键词:  直流系统  串联交流电源  测量精度  分布电容  电压纹波
英文关键词:DC  system, series  AC power  supply, measurement  accuracy, distributed  capacitance, Voltage  ripple
基金项目:
        
作者中文名作者英文名单位
周军Zhou Jun东北电力大学 电气工程学院
刘毕杰Liu Bijie东北电力大学 电气工程学院
李曙光Li Shuguang东北电力大学 电气工程学院
摘要点击次数: 1463
中文摘要:
      针对现阶段直流系统接地故障检测所使用的频率注入法会给直流系统带来较大纹波和受到分布电容影响较大的问题,本文提出了在正负直流母线间串联交流电源并在母线增加短路电容通路的方法以提高检测精度。即根据两次变频注入交流信号得到故障支路的漏电流建立两个二元方程以在规避分布电容影响的前提下精确求得接地电阻。该方法向母线投入一个大电容支路,既能有效规避母线分布电容给测量带来的误差,又满足国家电网的规定,向系统注入的小信号在纹波规定范围内,还从计算上规避了支路分布电容的影响。该方法有效减小了由于传感器测量精度和分布电容对直流系统绝缘检测带来的误差,降低了绝缘检测设备漏报误报概率,提高了检测精度并使用实验仿真验证了方法的可行性。
英文摘要:
      In view of the problem that the frequency injection method used in current DC system grounding fault detection will bring large ripples to the DC system and is greatly influenced by the distributed capacitance, this paper proposes a method to increase the detection precision by adding the AC power to the positive and negative DC buses and adding the short circuit capacitance path on the bus.That is the leakage current of the fault branch is obtained according to the two frequency conversion injection of AC signals,two two element equations are established to accurately calculate the earth resistance under the premise of avoiding the influence of distributed capacitance.This method can input a large capacitance branch in the bus bar, which can effectively avoid the error caused by the busbar distributed capacitance and meet the requirements of the State Grid.,and the small signal injected into the system is within the specified range of ripple,the influence of branch distribution capacitance is also avoided.The method effectively reduces the error caused by the sensor measurement precision and the distributed capacitance on the DC system insulation detection, reduces the false alarm probability of the insulation detection equipment, improves the detection precision and uses the experimental simulation to verify the feasibility of the method.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司