周文峰,杜志叶,张力,修连成,甘艳,邹建明.地质灾害对超高压输电线路杆塔杆件失效影响分析[J].电测与仪表,2020,57(7):16-22.
ZhouWenfeng,Du Zhiye,Zhang Li,Xiu Liancheng,Gan Yan,Zou Jianming.Effect of geological disasters on failure of UHV transmission line towers[J].Electrical Measurement & Instrumentation,2020,57(7):16-22.
地质灾害对超高压输电线路杆塔杆件失效影响分析
Effect of geological disasters on failure of UHV transmission line towers
DOI:10.19753/j.issn1001-1390.2020.07.003
中文关键词:  地质灾害  输电线路  杆塔  有限元分析  结构失效
英文关键词:geological disaster, transmission line, tower  finite element analysis, structural failure
基金项目:国家电网公司华中分部科技项目
                 
作者中文名作者英文名单位
周文峰ZhouWenfeng武汉大学电气与自动化学院
杜志叶Du Zhiye武汉大学电气与自动化学院
张力Zhang Li武汉大学电气与自动化学院
修连成Xiu Liancheng武汉大学电气与自动化学院
甘艳Gan Yan国家电网公司华中分部
邹建明Zou Jianming国家电网公司华中分部
摘要点击次数: 1446
中文摘要:
      地质灾害容易导致输电线路杆塔基础发生移动和变形,造成杆塔结构失效甚至损毁,严重影响输电线路的安全稳定运行。针对地质灾害导致的某500 kV杆塔结构受损问题,提出一种基于第四强度理论的判断杆件失效的方法,可准确判断杆件失效部位和失效程度。利用ANSYS软件建立杆塔精细化有限元模型,施加地质灾害下各工况塔基约束条件,基于失效判据对杆塔应力进行分析。结果表明:塔基沉降量达29 mm时,塔腿上横隔面交叉材屈曲失稳,沉降量达76 mm时,塔腿主材失效;塔基沉降和倾斜对杆塔破坏最为严重,塔基侧滑对杆塔影响较小。根据塔材失效的特点,提出杆塔结构加固及灾害监测与预防的建议。结合工程实际,为地质灾害下杆塔的稳定性分析及处理提供一定的指导作用。
英文摘要:
      Geological disasters are likely to cause movement and deformation of the transmission tower foundation, resulting in failure or even damage to the tower structure, seriously affecting the safe and stable operation of the transmission line. Aiming at the damage of a 500 kV tower caused by geological disasters, a method based on the fourth strength theory to judge the failure of the rod is proposed, which can accurately determine the failure position and failure degree of the rod. The ANSYS software was used to establish the refined finite element model of the tower, and the constraints of the tower foundation under various geological disasters were applied. The stress of the tower was analyzed based on the failure criterion. The results show that when the settlement of the tower base reaches 29 mm, the cross-section of the tower leg is buckling and unstable. When the settlement reaches 76 mm, the main material of the tower is ineffective; the settlement and inclination of the tower are the most serious damage to the tower. Side slip has less effect on the tower. According to the characteristics of tower failure, the suggestions for tower structure reinforcement and disaster monitoring and prevention are put forward. Combined with the actual project, it provides a certain guiding role for the stability analysis and treatment of the tower under geological disasters.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司