张宗喜,刘睿,聂鸿宇,龙震泽,赵莉华,安建国,任俊文.微氧作用下天然酯变压器油热老化特性研究[J].电测与仪表,2021,58(12):63-68.
Zhang Zongxi,Liu Rui,Nie Hongyu,Long Zhenze,Zhao Lihua,An Jianguo,Ren Junwen.Study on Thermal Aging Characteristics of Natural Ester Transformer Oil under Micro-Oxygen[J].Electrical Measurement & Instrumentation,2021,58(12):63-68.
微氧作用下天然酯变压器油热老化特性研究
Study on Thermal Aging Characteristics of Natural Ester Transformer Oil under Micro-Oxygen
DOI:10.19753/j.issn1001-1390.2021.12.009
中文关键词:  天然酯绝缘油  微氧作用  热老化  电气性能  油色谱
英文关键词:natural  ester insulation  oil, Microoxygenation, thermal  aging, electrical  properties, oilchromatograp
基金项目:国家电网有限公司科技项目资助(521997180018);“特高压工程技术(昆明、广州)国家工程实验室”开放基金资助
                    
作者中文名作者英文名单位
张宗喜Zhang Zongxi四川省电力科学研究院
刘睿Liu Rui四川省电力科学研究院
聂鸿宇Nie Hongyu国网广元供电公司
龙震泽Long Zhenze四川省电力科学研究院
赵莉华Zhao Lihua四川大学电气工程学院
安建国An Jianguo四川大学
任俊文Ren Junwen四川大学电气工程学院
摘要点击次数: 1523
中文摘要:
      天然酯变压器油因不饱和脂肪酸含量较高而易氧化,而变压器因储油罐与空气作用或密封设备产生泄漏等原因,会导致油中溶解微量的氧气。基于此,本文对微氧作用下天然酯变压器油的热老化特性进行了研究,分析了不同老化时间下油样的电气性能、油色谱特性以及两者之间的皮尔逊相关系数。结果表明:适时微氧作用能在一定程度上延缓天然酯变压器油电气性能的降低;天然酯变压器油纸绝缘热老化的特征气体为CO2和C2H6;天然酯变压器油的电气性能与油色谱中CO2-C2H6(油样中溶解的CO2与C2H6的百分比之差)之间存在强相关性。
英文摘要:
      Natural ester transformer oil is easy to oxidize due to its high content of unsaturated fatty acid, while the transformer will dissolve a small amount of oxygen in the oil due to the effect of oil tank and air or leakage of sealing equipment. Based on this, the thermal aging characteristics of natural ester transformer oil under micro-oxygen were studied, the electrical properties, oil chromatogram characteristics and Pearson correlation coefficient of the oil samples under different aging time are analyzed. The results show that the electrical properties of natural ester transformer oil can be delayed to some extent by the action of timely micro-oxygen; the characteristic gases of thermal aging of oil-paper insulation of natural ester transformer are CO2 and C2H6; there is a strong correlation between the electrical properties of natural ester transformer oil and CO2-C2H6 (the percentage difference between dissolved CO2 and C2H6 in oil samples) in the oil chromatogram.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司