毛成程,王巨丰,周勇军,孟伟航,韩力.10 kV配电网压缩灭弧防雷装置工频续流遮断与雷电冲击实验研究[J].电测与仪表,2022,59(10):38-44.
maochengcheng,wangjufeng,zhouyongjun,mengweihang,hanli.Research on power frequency follow current interruption and lightning impulse experiment of 10 kV distribution network compression arc extinguishing and lightning protection device[J].Electrical Measurement & Instrumentation,2022,59(10):38-44.
10 kV配电网压缩灭弧防雷装置工频续流遮断与雷电冲击实验研究
Research on power frequency follow current interruption and lightning impulse experiment of 10 kV distribution network compression arc extinguishing and lightning protection device
DOI:DOI: 10.19753/j.issn1001-1390.2022.10.006
中文关键词:  配网线路  压缩灭弧防雷装置  工频续流  绝缘配合  伏秒特性
英文关键词:distribution line, compression arc extinguishing and lightning protection device, power frequency follow current, insulation coordination, volt-second characteristics
基金项目:国家自然科学基金项目( 51467002)
              
作者中文名作者英文名单位
毛成程maochengcheng广西大学
王巨丰wangjufeng广西大学
周勇军zhouyongjun广西大学
孟伟航mengweihang广西大学
韩力hanli广西大学
摘要点击次数: 1334
中文摘要:
      针对配电网络通常不架设避雷线, 雷击时极易引起闪络跳闸的情况, 研究了一种应用于10 kV线路的具备灭弧能力的防雷装置。压缩灭弧装置本质上是一种带有灭弧能力的并联间隙, 为验证其有效性, 对其分别进行了遮断灭弧实验以及雷电冲击放电实验, 实验结果表明: 该装置能在4 ms内熄灭电弧且有抑制重燃的效果;通过雷电冲击实验得到了该装置在干弧长度为22.5 cm的支柱绝缘子下的间隙长度为5 cm、7 cm、9 cm的伏秒特性曲线, 分析其伏秒特性曲线, 最终得出适合此类绝缘子的间隙长度是不超过7.4 cm, 为日后的工程安装提供理论指导。
英文摘要:
      In view of the fact that the distribution network usually does not set up lightning wires, which is easy to cause flashover and trip when lightning strikes, this paper studies a lightning protection device with arc extinguishing capability applied to 10 kV lines. The compression arc extinguishing device is essentially a kind of parallel gap with arc extinguishing capability. In order to verify its effectiveness, the experiments of interrupting arc extinguishing and lightning impulse discharge are carried out respectively. The experimental results show that the device can extinguish the arc within 4 ms and achieve the effect of restraining re-ignition. Through the lightning impulse test, the Volt-second characteristic curve of the device with the gap length of 5 cm, 7 cm and 9 cm under the post insulator with the dry arc length of 22.5 cm is obtained, and the V-s characteristic curve is analyzed. Finally, the gap length suitable for this kind of insulator is not more than 7.4 cm, which provides theoretical guidance for the future engineering installation.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司