杨智,詹江杨,徐 星,玉林威,邹国平,陈向荣.变压器中性点过电压分析与绝缘配合[J].电测与仪表,2023,60(10):30-35.
Yang Zhi,Zhan Jiangyang,Xu Xing,Yu Linwei,Zou Guoping,Chen Xiangrong.Overvoltage analysis and insulation coordination of transformer neutral point[J].Electrical Measurement & Instrumentation,2023,60(10):30-35.
变压器中性点过电压分析与绝缘配合
Overvoltage analysis and insulation coordination of transformer neutral point
DOI:10.19753/j.issn1001-1390.2023.10.005
中文关键词:  110 kV输电系统  变压器中性点  过电压  放电间隙  绝缘配合
英文关键词:110 kV transmission system, neutral point of transformer, overvoltage, discharge gap, insulation coordination
基金项目:国网浙江省电力有限公司科技项目(5211DS180039)
                 
作者中文名作者英文名单位
杨智Yang Zhi国网浙江省电力有限公司电力科学研究院
詹江杨Zhan Jiangyang国网浙江省电力有限公司电力科学研究院
徐 星Xu Xing浙江大学电气工程学院
玉林威Yu Linwei浙江大学电气工程学院
邹国平Zou Guoping浙江大学电气工程学院
陈向荣Chen Xiangrong浙江大学电气工程学院
摘要点击次数: 947
中文摘要:
      电力系统发生不对称短路、非全相运行和雷击等故障时,变电站变压器中性点会出现较高的过电压,严重影响中性点绝缘的可靠性,因此需要对变压器中性点过电压和绝缘配合开展研究。文章在PSCAD/EMTDC中搭建110 kV输电系统仿真模型,计算分析线路发生各种故障时的中性点过电压,依据仿真所得过电压值,确定放电间隙距离以实现更加优化的绝缘配合。结果表明,线路发生单相接地故障时中性点最高过电压为117.73 kV;发生单相断线时中性点最高过电压为52 kV;发生雷击时中性点最高过电压为118 kV;采用放电间隙并联避雷器的中性点保护方式时,选取放电间隙距离为13 mm~14 mm时能达到最优的绝缘配合效果。该研究结果可以为110 kV变压器中性点的绝缘配合优化提供重要的理论和实验参考依据。
英文摘要:
      When the 110 kV power system suffers from asymmetrical short circuit, non-full-phase operation, and lightning strikes, a large overvoltage will appear at the neutral point of the transformer in the substation and endanger the neutral point insulation. Therefore, it is necessary to study the over-voltage and insulation coordination of transformer neutral points. This paper builds a simulation model of 110 kV power transmission system in PSCAD/EMTDC, calculates and analyzes the neutral point overvoltage when various faults occur on the line, and determines the discharge gap distance based on the obtained overvoltage value to achieve good insulation coordination. The calculation results show that the maximum overvoltage at the neutral point reaches 117.73 kV when a single-phase ground fault occurs on the line; the maximum overvoltage at the neutral point reaches 52 kV when a single-phase disconnection occurs; the maximum overvoltage at the neutral point reaches 118 kV when a lightning strike occurs; a better insulation coordination effect can be achieved when the discharge gap distance is 13 mm~14 mm with the parallel arrester. The research results can provide important theoretical and experimental reference basis for insulation coordination of 110 kV transformer neutral point.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司