• 设为首页
  • 加入收藏
  • 联系邮箱
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
  • English
站内检索    
 
生西奎,付强,于洋,吴昊,杨凌.基于深度学习GRU网络的配电网理论线损计算方法[J].电测与仪表,2021,58(3):54-59.
Sheng Xikui,Fu Qiang,Yu Yang,Wu Hao,Yang Ling.Distribution network line loss calculation methodbased on deep learning GRU network[J].Electrical Measurement & Instrumentation,2021,58(3):54-59.
基于深度学习GRU网络的配电网理论线损计算方法
Distribution network line loss calculation methodbased on deep learning GRU network
DOI:10.19753/j.issn1001-1390.2021.03.009
中文关键词:  理论线损  互信息  层次分析法  门控循环单元
英文关键词:theoretical  line loss, mutual  information, analytic  hierarchy process, gated  recurrent unit
基金项目:
              
作者中文名作者英文名单位
生西奎Sheng Xikui国网吉林省电力有限公司延边供电公司
付强Fu Qiang东北电力大学 电气工程学院
于洋Yu Yang国网延吉市城郊供电公司
吴昊Wu Hao国网吉林省电力有限公司延边供电公司
杨凌Yang Ling国网吉林省电力有限公司延边供电公司
摘要点击次数: 1448
中文摘要:
      由于实际应用中对理论线损的精度要求不高,且传统计算方法所需电气参数较多,计算过程繁琐。因此,文中提出了一种基于深度学习门控循环单元(Gated Recurrent Unit, GRU)网络的配电网理论线损计算方法。首先,为了综合考虑主客观因素,将互信息理论和层次分析法相结合,进而确定所选电气参数对理论线损影响的权重;然后,按照权重的大小构建不同的输入参数集,通过分析选用不同电气参数集时GRU网络的计算误差,确定最优输入参数,组成样本数据集并训练GRU网络;最后,以某地区10 kV配电网为例验证了文中所提方法,分析结果表明,文中所提方法可以代替等值电阻法,更加快速、便捷地对理论线损进行计算。文中所提方法还与传统BP算法进行了比较,结果表明文中所提方法具有更好的计算性能。
英文摘要:
      The accuracy of theoretical line loss calculation is not high in practical application, in addition, calculation method requires many electrical parameters and the process is tedious. Therefore, the paper proposes a theoretical line loss calculation method based on deep learning gated recurrent unit (GRU). Firstly, considering the subjective and objective factors, the correlation between the electrical parameters and the theoretical line loss is calculated by the combination of mutual information and analytic hierarchy process. Then, different input parameter sets were set according to the size of weight. Through the analysis of the calculation error of the GRU network, the optimal input parameters are determined and form the sample data of training the GRU network. Finally, this method is verified by taking a 10 kV distribution network as an example. The results show that this method can replace the equivalent resistance method and calculate the theoretical line loss more quickly and conveniently. Compared with the traditional BP algorithm, this method has better performance.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司