• 设为首页
  • 加入收藏
  • 联系邮箱
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
  • English
站内检索    
 
范慧芳,咸日常,刘兴华,张冰倩,陈蕾,高鸿鹏.基于能量系数的电力变压器热故障严重性评估方法[J].电测与仪表,2024,61(2):83-88.
FAN Huifang,XIAN Richang,LIU Xinghua,ZHANG Bingqian,CHEN Lei,GAO Hongpeng.Evaluation method of thermal fault severity of power transformer based on energy coefficient[J].Electrical Measurement & Instrumentation,2024,61(2):83-88.
基于能量系数的电力变压器热故障严重性评估方法
Evaluation method of thermal fault severity of power transformer based on energy coefficient
DOI:10.19753/j.issn1001-1390.2024.02.012
中文关键词:  电力变压器  热故障  严重程度  能量系数  最大熵原理
英文关键词:power transformer, thermal failure, severity, energy coefficient, maximum entropy principle
基金项目:国家“十三五”重点研发计划(2016YFB0901303);国网山东省电力公司科技项目(SGSDZZ00FZJS2000562)
                 
作者中文名作者英文名单位
范慧芳FAN Huifang山东理工大学
咸日常XIAN Richang山东理工大学
刘兴华LIU Xinghua国网山东省电力公司淄博供电公司
张冰倩ZHANG Bingqian山东理工大学
陈蕾CHEN Lei山东理工大学
高鸿鹏GAO Hongpeng山东理工大学
摘要点击次数: 1010
中文摘要:
      运行电力变压器内部的热点温度直接影响其使用寿命和运行可靠性。为准确评估电力变压器内部过热故障的严重程度,文章借助焓变理论提出一种计算故障能量系数的方法,为故障赋予一定的权值系数;并基于能量系数这一概念,以电力变压器各类不同程度的热故障为研究对象,建立其严重程度分级评估基准,此基准是以563组电力变压器热故障油色谱分析数据所计算出的能量系数值作为样本数据,利用最大熵原理得出最符合实际分布的电力变压器热故障能量系数概率分布函数,并求取其分位值Q20、Q70和Q95作为热故障严重程度的分级评估值。经实际算例分析,采用文中所提方法,不仅可以实现对热故障严重程度的量化评估,还可以合理地划分其严重等级,可为检修人员制定和执行维护计划提供参考。
英文摘要:
      The hot spot temperature inside the operating power transformer directly affects its service life and operational reliability. In order to accurately evaluate the severity of the internal overheating fault of a power transformer, this paper firstly used the theory of enthalpy change to propose a novel method for calculating the fault energy coefficient, and assigned a certain weight coefficient to the fault; Secondly, based on the concept of energy coefficient, different degrees of thermal failures for various types of power transformers were the research objects, and the severity level evaluation criteria were established. This benchmark was based on the energy coefficient values calculated from the chromatographic analysis data of the 563 groups of power transformer thermal faults as the sample data, and the principle of maximum entropy was used to obtain the most consistent actual distribution of power transformer thermal fault energy coefficient probability distribution function, and the quantile values Q20, Q70 and Q95 were calculated as the graded evaluation value of the thermal fault severity. Finally, the method proposed in this paper could not only realize the quantitative assessment of the severity of thermal faults, but also reasonably divide the severity levels through analyzing the actual calculation examples, which can provide references for maintenance personnel to formulate and implement maintenance plans.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 历任主编
    • 期刊荣誉
  • 编委会
    • 社长及主编
    • 主任委员
    • 编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司