• 设为首页
  • 加入收藏
  • 联系邮箱
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 社长及主编
    • 期刊荣誉
  • 编委会
    • 主任委员
    • 编委名单
    • 青年编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
  • English
站内检索    
 
汪本进,王睿晗,吴士普,叶子阳,徐思恩.特高压直流电压互感器换热结构设计及其对误差特性的影响研究[J].电测与仪表,2022,59(1):84-92.
Wang Benjin,Wang Ruihan,Wu Shipu,Ye Ziyang,Xu Sien.Research on the heat exchange structure designing for UHV DCVT and its influence on error characteristics[J].Electrical Measurement & Instrumentation,2022,59(1):84-92.
特高压直流电压互感器换热结构设计及其对误差特性的影响研究
Research on the heat exchange structure designing for UHV DCVT and its influence on error characteristics
DOI:10.19753/j.issn1001-1390.2022.01.011
中文关键词:  直流电压互感器  涡旋式换热器  轴向温差  分压比误差
英文关键词:DCVT, vortex heat exchanger, axial temperature difference, voltage division ratio error
基金项目:国家电网公司总部科技项目资助(超/特高压直流电压互感器研制及试验关键技术研究,项目合同号GYW17201800038)
              
作者中文名作者英文名单位
汪本进Wang Benjin中国电力科学研究院有限公司武汉分院,武汉 430074
王睿晗Wang Ruihan国网四川省电力公司,成都 610064
吴士普Wu Shipu中国电力科学研究院有限公司武汉分院,武汉 430074
叶子阳Ye Ziyang国网四川省电力公司,成都 610064
徐思恩Xu Sien中国电力科学研究院有限公司武汉分院,武汉 430074
摘要点击次数: 1485
中文摘要:
      为解决直流电压互感器(DCVT)电阻温升造成的测量准确度问题,文章对±800 kV DCVT换热问题进行了研究。分析了电阻选择原则,在此基础上进行了DCVT的设计,重点设计了DCVT的换热结构。通过采用涡旋式换热配合双气式结构来达到优化换热方式降低因电阻温升带来的误差的目的。为验证设计效果,建立了考虑SF6物性参数随温度变化的三维DCVT内部温升计算模型。计算结果表明:论文设计的换热器可使DCVT内部总体温升下降10.5%,轴向温差下降43%。因电阻温升产生的测量误差仅为0.025%,符合设计要求。为进一步验证换热效果,进行了温升对分压比影响的试验。试验结果表明:温升条件下DCVT分压比的误差小于0.2级误差限值。理论与试验均表明:论文设计的涡旋式换热结构可使电阻温升导致的误差远小于要求的误差限值,可保证DCVT具有很好的测量精度。
英文摘要:
      In order to solve the measurement accuracy problem caused by the temperature rise of DC voltage transformers (DCVT) resistance, this paper has been studied the heating problem for ±800 kV DCVT. The principle of resistance selection is analyzed. On this basis, the DCVT design is performed, and the heat exchange structure of DCVT is designed. Through the adoption of vortex type heat exchanger with double gas type structure is adopted to optimize the heat exchange mode and reduce the error caused by the temperature rise of resistance. To verify the design effect, a three-dimensional DCVT internal temperature rise calculation model is established considering the change of SF6 physical parameters with temperature. The calculation results show that the designed heat exchanger can reduce the internal overall temperature rise of the DCVT to 10.5%, and the axial temperature difference is reduced by 43%, and the measurement error generated by the resistance temperature rise is 0.025%, which meets the design requirements. In order to further verify the heat exchange effect, and the test of temperature rise on the voltage division ratio is carried out. Experimental results show that under the condition of temperature rise, DCVT voltage division ratio error is less than 0.2 class error limit. Both theoretical and experimental results show that the vortex heat exchange structure designed in this paper enables that the error caused by resistance temperature rise is much smaller than the required error limit, and ensures the DCVT has good measurement accuracy.
查看全文  查看/发表评论  下载PDF阅读器
关闭
  • 哈尔滨电工仪表研究所有限公司
  • 中国电工仪器仪表信息网
  • 中国仪器仪表学会
  • 中华人民共和国新闻出版总署
  • 中国科技期刊编辑学会
  • 黑龙江省科学技术协会
  • 编辑之家
  • 中国知网
  • 万方数据库
  • 维普网
  • 北极星电力网
  • 中华中控网
  • 网站首页
  • 期刊介绍
    • 期刊简介
    • 社长及主编
    • 期刊荣誉
  • 编委会
    • 主任委员
    • 编委名单
    • 青年编委名单
  • 投稿指南
    • 作者须知
    • 投稿步骤
    • 范文(规范细则)
    • 稿件处理流程
    • 著作权转让协议
  • 期刊影响力
  • 开放获取
  • 出版道德政策
    • 出版伦理声明
    • 学术不端认定和处理方法
    • 广告及市场推广
    • 同行评议流程
    • 斟误和撤回
    • 回避制度
    • 文章署名及版权转让
  • 历年目次
  • 联系我们
地址:哈尔滨市松北区创新路2000号    邮编:150028
邮箱:dcyb@vip.163.com    电话:0451-86611021;87186023
© 2012 电测与仪表    哈公网监备2301003445号
黑ICP备11006624号-1
技术支持:北京勤云科技发展有限公司