典型交直型电气化铁路对直驱风电场运行的影响研究
Study of the Effect of Typical AC-DC Electrified Railway on the Direct-drive Wind Farm Operation
Received:May 29, 2014  Revised:June 24, 2014
DOI:
中文关键词: 交直型机车  V/v牵引变压器  三相不平衡  直驱型风电机组  正负序双电流控制
英文关键词: AC/DC electric locomotive  V/v connected traction transformer  three-phase imbalance  direct driven wind turbine  positive and negative sequence dual current control strategy
基金项目:国家自然科学(51177112)Project Supported by the National Natural Science Foundation of China(NSFC)(51177112).
Author NameAffiliationE-mail
wangyingxiang* WUhan university 50893862@qq.com 
Cui xue wuhan university  
wuhan university wuhan university  
Lichenying wuhan university  
Hits: 2847
Download times: 1036
中文摘要:
      介绍了电气化铁路对于风电场运行的影响。针对运用广泛的交直传动型电力机车进行说明,介绍了典型交直传动型机车的接线方式及其结构特点。选取使用三相V/v接线方式的牵引变电站进行研究,分析了其产生三相不平衡的机理以及其接入电网后带给风电接入点的电能质量问题。在交直型机车接入风电并网点的背景下,研究了直驱风电机组在三相不平衡条件下产生直流侧二倍频波动的机理,提出了一种以稳定直流侧电压为目的正负序双电流控制策略。最后,在PSCAD中,对交直型机车与直驱风电场进行建模并接入桂林电网,验证该类电气化铁路给风电场带来的电能质量问题,仿真直驱型风电机组在三相不平衡条件下利用正负序双电流控制策略的运行情况。
英文摘要:
      The impact of railway to wind farm is introduced. An introduction about the AC/DC electric locomotive which is used widely and its tractive power supply system is made,and its wiring and structural features are introduced. The typical traction substation which uses three phase V/v connected traction transformer is chose to be studied. After that, the generation of the three-phase imbalance and the power quality problems of wind farm caused by the AC/DC electrified railway are studied. The principle of the generation of second harmonic fluctuation in direct driven turbine DC side,and a positive and negative sequence dual current control strategy is presented for direct driven wind turbine under the circumstance that the AC/DC electric locomotive is connected to wind farm. At last, the model of AC/DC electric locomotive and direct driven wind farm are established, and the power quality problems of wind farm caused by the AC/DC electrified railway is validated, also the running situation of direct driven wind turbine with positive and negative sequence dual current control strategy under three-phase imbalance is simulated.
View Full Text   View/Add Comment  Download reader
Close
  • Home
  • About Journal
    • Historical evolution
    • Journal Honors
  • Editorial Board
    • Members of Committee
    • Director of the Committee
    • President and Editor in chief
  • Submission Guide
    • Instructions for Authors
    • Manuscript Processing Flow
    • Model Text
    • Procedures for Submission
  • Academic Influence
  • Open Access
  • Ethics&Policies
    • Publication Ethics Statement
    • Peer Review Process
    • Academic Misconduct Identification and Treatment
    • Advertising and Marketing
    • Correction and Retraction
    • Conflict of Interest
    • Authorship & Copyright
  • Contact Us
  • 中文页面
Address: No.2000, Chuangxin Road, Songbei District, Harbin, China    Zip code: 150028
E-mail: dcyb@vip.163.com    Telephone: 0451-86611021
© 2012 Electrical Measurement & Instrumentation
黑ICP备11006624号-1
Support:Beijing Qinyun Technology Development Co., Ltd