文章摘要
配电网单相接地故障脉冲电流测距
Fault location for single-phase grounding fault of distribution network based on pulse current
Received:September 12, 2017  Revised:September 12, 2017
DOI:
中文关键词: 故障测距  脉冲电流测距  消弧线圈  中性点非有效接地系统
英文关键词: fault  location, fault  location based  on pulse  current, arc  suppression coil, non-effectively  grounded neutral
基金项目:
Author NameAffiliationE-mail
Liu Xiaojiang State Grid Sichuan Electric Power Research Institute 13408548341@163.com 
Chen Kunyi* Sichuan university ky0304528@163.com 
Xiao Xianyong Sichuan university xiaoxianyong@163.com 
Fan Songhai State Grid Sichuan Electric Power Research Institute 879238566@qq.com 
Hits: 1665
Download times: 529
中文摘要:
      针对配网单相接地故障电流较小,测距困难的问题,提出了一种脉冲电流测距方法。该方法通过短时改变中性点接地方式,在故障线路上产生幅值较大的脉冲电流。合理选择连接于中性点的限流电阻,将暂态过程控制在脉冲电流前半段,采用后半段数据计算脉冲电流稳态特征。利用脉冲电流稳态特征与故障距离之间的关系,实现了脉冲电流故障测距。该方法用于测距的脉冲电流幅值较大,可有效解决单相接地故障测距问题。通过MATLAB/simulink仿真表明该方法具有较高的精度且受接地电阻影响较小。
英文摘要:
      A fault location method based on pulse current is presented, this method aimed to deal with the problem that the position of fault can’t be calculated accurately because the amplitude of single-phase grounding fault current is very smaller. A large amplitude pulse current is produced in fault line through changing the neutral grounding model in a short time. The transient process of pulse current can be controlled in the range of first half through selecting the current limiting resistance reasonably, and the second half of pulse current can be used to calculate the steady character of pulse current. The fault location method can be implement according to the relations between the steady character of pulse current and the fault position. The simulations with MATLAB/simulink software show that the presented fault location method has a high precision and little effect by ground resistance.
View Full Text   View/Add Comment  Download reader
Close
  • Home
  • About Journal
    • Historical evolution
    • Journal Honors
  • Editorial Board
    • Members of Committee
    • Director of the Committee
    • President and Editor in chief
  • Submission Guide
    • Instructions for Authors
    • Manuscript Processing Flow
    • Model Text
    • Procedures for Submission
  • Academic Influence
  • Open Access
  • Ethics&Policies
    • Publication Ethics Statement
    • Peer Review Process
    • Academic Misconduct Identification and Treatment
    • Advertising and Marketing
    • Correction and Retraction
    • Conflict of Interest
    • Authorship & Copyright
  • Contact Us
  • 中文页面
Address: No.2000, Chuangxin Road, Songbei District, Harbin, China    Zip code: 150028
E-mail: dcyb@vip.163.com    Telephone: 0451-86611021
© 2012 Electrical Measurement & Instrumentation
黑ICP备11006624号-1
Support:Beijing Qinyun Technology Development Co., Ltd