随桥电缆-架空混合线路的电缆护套过电压特性仿真分析
Simulation analysis of overvoltage characteristics of cable sheath for bridge cable-overhead hybrid line
Received:September 28, 2020  Revised:October 01, 2020
DOI:10.19753/j.issn1001-1390.2024.02.007
中文关键词: 随桥电缆  混合线路  雷击故障  操作故障  过电压特性  绝缘配合
英文关键词: bridge-cable, hybrid line, lightning fault, operation fault, overvoltage characteristics, insulation coordination
基金项目:浙江省自然科学基金项目(LY18E070003);浙江大学“百人计划”(自然科学A类)
Author NameAffiliationE-mail
QIU Lifeng Zhejiang Huayun Power Engineering Design Consulting Company qiulifeng_1@163.com 
DU Zhendong Zhejiang Huayun Power Engineering Design Consulting Company xuxingabcd@qq.com 
ZHOU Wenjun Zhejiang Huayun Power Engineering Design Consulting Company xuxingabcd@qq.com 
XU Xing Zhejiang Provincial Key Laboratory of Electrical Machine Systems, College of Electrical Engineering, Zhejiang University xuxingabcd@qq.com 
CHEN Xiangrong* Zhejiang Provincial Key Laboratory of Electrical Machine Systems, College of Electrical Engineering, Zhejiang University chenxiangrongxh@zju.edu.cn 
Hits: 1012
Download times: 281
中文摘要:
      随桥电缆作为跨海输电系统的重要组成部分,其安全稳定运行对于整个输电系统的可靠性有重要影响。论文以舟岱大桥220 kV随桥电缆工程为研究对象,考虑架空线路的影响,基于PSCAD/EMTDC暂态仿真软件建立了随桥电缆-架空混合线路的仿真模型,对雷击故障和操作故障下的电缆护套过电压特性进行了研究。结果表明:雷击架空线路时,护套过电压幅值随故障距离的减小而增大,随杆塔接地电阻的增大而增大,过电压幅值最高可达到46.4 kV;单相接地故障下,接地相角为90°时护套过电压最严重,过电压幅值最高可达到15.9 kV;非全相操作故障下,电缆护套过电压幅值受故障距离的影响不大,两相断线的护套过电压比单相断线更严重。研究工作为随桥电缆-架空混合线路的绝缘配合设计提供了参考依据。
英文摘要:
      As an important part of the cross-sea transmission system, the bridge-cable has an important impact on the reliability of the entire transmission system. Taking the 220 kV bridge-cable engineering of Zhoudai Bridge as the research object, considering the influence of overhead lines, a simulation model of the bridge cable-overhead hybrid line is established based on PSCAD/EMTDC transient simulation software. The overvoltage characteristics of the cable sheath under lightning strike and operation fault are studied. The results show that when lightning strikes the overhead line, the sheath overvoltage amplitude increases with the decrease of the strike distance, and with the increase of the tower grounding resistance, the maximum overvoltage amplitude can reach up to 46.4 kV, under a single-phase grounding fault, the sheath overvoltage is the most serious when the ground phase angle is 90°, and the maximum overvoltage amplitude can reach up to 15.9 kV, under a non-full-phase operation fault, the cable sheath overvoltage amplitude is not greatly affected by the fault distance. The sheath overvoltage of two-phase disconnection is more serious than that of single-phase disconnection. The research work provides a certain reference for the insulation coordination design of the bridge cable-overhead hybrid line.
View Full Text   View/Add Comment  Download reader
Close
  • Home
  • About Journal
    • Historical evolution
    • Journal Honors
  • Editorial Board
    • Members of Committee
    • Director of the Committee
    • President and Editor in chief
  • Submission Guide
    • Instructions for Authors
    • Manuscript Processing Flow
    • Model Text
    • Procedures for Submission
  • Academic Influence
  • Open Access
  • Ethics&Policies
    • Publication Ethics Statement
    • Peer Review Process
    • Academic Misconduct Identification and Treatment
    • Advertising and Marketing
    • Correction and Retraction
    • Conflict of Interest
    • Authorship & Copyright
  • Contact Us
  • 中文页面
Address: No.2000, Chuangxin Road, Songbei District, Harbin, China    Zip code: 150028
E-mail: dcyb@vip.163.com    Telephone: 0451-86611021
© 2012 Electrical Measurement & Instrumentation
黑ICP备11006624号-1
Support:Beijing Qinyun Technology Development Co., Ltd